1) Calculate the apparent power in KVA of 3 phase 415V, 50 Hz, star system, if the line current (IL) is 16A at 0.8 power factor.
15.2 KVA
11.5 KVA
9.2 KVA
5.3 KVA
Show Answer
Report Question
What's wrong with this question?
Report
Correct Answer: 11.5 KVA
Question Details
1) Calculate the apparent power in KVA of 3 phase 415V, 50 Hz, star system, if the line current (IL) is 16A at 0.8 power factor.
15.2 KVA
11.5 KVA
9.2 KVA
5.3 KVA
2) What will be the readings of two watt meters (W1& W2) in 3 phase power measurement, if the power factor is zero?
W1 & W2 both are positive reading
W1 is Positive and W2 is negative reading
W1 is equal to W2 but with opposite signs
Zero W1 is Positive reading, and W2 is negative reading
Show Answer
Report Question
What's wrong with this question?
Report
Correct Answer: W1 is equal to W2 but with opposite signs
Question Details
2) What will be the readings of two watt meters (W1& W2) in 3 phase power measurement, if the power factor is zero?
W1 & W2 both are positive reading
W1 is Positive and W2 is negative reading
W1 is equal to W2 but with opposite signs
Zero W1 is Positive reading, and W2 is negative reading
3) What is the maximum value of voltage for 240 volt RMS?
240V
415V
339.5V
376.8V
Show Answer
Report Question
What's wrong with this question?
Report
Correct Answer: 339.5V
Question Details
3) What is the maximum value of voltage for 240 volt RMS?
240V
415V
339.5V
376.8V
4) What is the phase displacement in a single phase AC circuit?
90 Degree
120 Degree
180 Degree
270 Degree
Show Answer
Report Question
What's wrong with this question?
Report
Correct Answer: 90 Degree
Question Details
4) What is the phase displacement in a single phase AC circuit?
90 Degree
120 Degree
180 Degree
270 Degree
5) Calculate the line current of the 3 phase 415V 50 HZ supply for the balanced load of 3000 watt at 0.8 power factor is connected in star.
8.5 A
5.2 A
4.5 A
3.4 A
Show Answer
Report Question
What's wrong with this question?
Report
Correct Answer: 5.2 A
Question Details
5) Calculate the line current of the 3 phase 415V 50 HZ supply for the balanced load of 3000 watt at 0.8 power factor is connected in star.
8.5 A
5.2 A
4.5 A
3.4 A